Console management controller (cpqcmc.mib) – HP Insight Management for Tivoli User Manual

Page 65

Advertising
background image

Appendix B: HP SNMP events 65


Trap types

Rules file

Description

Netcool

severity

cpqRackServerBladePoweredOff(
22070)

22070

This event occurs when the
server blade is powered off.

Clear (0)

cpqRackInformationalEAETrap(22
071)

22071

This event occurs for EAE
Informational trap.

Clear(0)

cpqRackMinorEAETrap(22072)

22072

This event occurs for EAE Minor

trap.

Major(4)

cpqRackMajorEAETrap(22073)

22073

This event occurs for EAE Major

trap.

Critical(5)

cpqRackCriticalEAETrap(22074) 22074

This event occurs for EAE

Critical trap.

Critical(5)

cpqRackPowerMinorEAETrap(220

75)

22075

This event occurs when

FlexFabric Cmdr Power
Subsystem Minor trap occurs.

Minor(3)

cpqRackPowerMajorEAETrap(22
076)

22076

This event occurs when
FlexFabric Cmdr Power

Subsystem Major trap occurs.

Major(4)

cpqRackPowerCriticalEAETrap(22

077)

22077

This event occurs when

FlexFabric Cmdr Power
Subsystem Critical trap occurs.

Critical(5)

Console management controller (CPQCMC.MIB)

Trap types

Rules file

Description

Netcool

severity

cpqCmcalarmTemp1 (153001)

This event occurs when the
temperature at rack sensor 1 is

outside the specified threshold.

CpqCmcStatusTemp1: normal

CpqCmcStatusTemp1

.2

Clear (0)

CpqCmcStatusTemp1:Minor (3)

CpqCmcStatusTemp1

.3

Minor (3)

CpqCmcStatusTemp1:overMax

CpqCmcStatusTemp1

.4

Major (4)

CpqCmcStatusTemp1:underMin

CpqCmcStatusTemp1

.5

Major (4)

CpqCmcStatusTemp1:noSensor

CpqCmcStatusTemp1

.6

Major (4)

CpqCmcStatusTemp1:error

CpqCmcStatusTemp1
.7

Critical (5)

cpqCmcalarmTemp2 (153002)

This event occurs when the
temperature at rack sensor 2 is

outside the specified threshold.

CpqCmcStatusTemp2:normal

CpqCmcStatusTemp2

.2

Clear (0)

CpqCmcStatusTemp2:Minor (3)

CpqCmcStatusTemp2

.3

Minor (3)

Advertising