7.1.7.2 Relay connection

Relays are located inside R1A and R1B (Relay 1) and

inside R2A and R2B (Relay 2) connectors. Relays do

not have polarity and therefore both terminals A or

B of the same relay can be used, for alternating or

continuous current voltages.

RELAY CONNECTION

Terminal

Description

R1A

Relay 1, Terminal A

R1B

Relay 1, Terminal B

R2A

Relay 2, Terminal A

R2B

Relay 2, Terminal B

Tab. 4

Relays can be used for low working

voltages only (up to 30Vac or 60Vdc) and

with a maximum current of 1A. Use cables

with a section suitable for the load to be

controlled and use cables with a minimum

section of 0.25mm² (AWG 30) and maximum

section of 1.5mm² (AWG 16).

For further details on configuring and using the

relays, refer to 9.1.12.1 Alarms Menu, page 43.

7.1.7.3 Connecting the dusk switch for the

LED illuminator

During installation do not look directly at

the illuminator while it is on.

To guarantee correct vision during the day

and the night, it is necessary to correctly set

the sensor.

The dusk switch must be positioned so that

it is not hit by the light beam coming from

the illuminator or by artificial lights (such as

road lights, car headlights, etc.).