• Connect the device to a power source

corresponding to the indications given on the

marking label. Before proceeding with installation

make sure that the power line is properly isolated.

The supply voltage should never exceed the limit

(+/-10%).

• The device should be mounted so that it is

accessible only to the technician/installer because

the moving parts constitute a residual risk of injury

caused by movement of said parts.

• Attach the Dangerous Moving Parts label near the

device. (Fig. 1, page 12).

• The appliance should only be considered switched

off when the power supply has been disconnected

and the connecting cables to other devices have

been removed.

• A disconnecting device, readily and easily

accessible, must be incorporated in the electrical

system of the building for rapid intervention.

• Use a Class 2 listed UL tranformer, compliant with

the Standards in force, only for products marked

UL, powered at 24Vac.

• Installation category (also called Overvoltage

Category) specifies the level of mains voltage

surges that the equipment will be subjected to.

The category depends upon the location of the

equipment, and on any external surge protection

provided. Equipment in an industrial environment,

directly connected to major feeders/short branch

circuits, is subjected to Installation Category III. If

this is the case, a reduction to Installation Category

II is required. This can be achieved by use of an

insulating transformer with an earthed screen

between primary and secondary, or by fitting

listed Surge Protective Devices (SPDs) from live

to neutral and from neutral to earth. Listed SPDs

shall be designed for repeated limiting of transient

voltage surges, suitable rated for operating voltage

and designated as follows: Type 2 (Permanently

connected SPDs intended for installation on the

load side of the service equipment overcurrent

device); Nominal Discharge Current (In) 20kA min.

For example: FERRAZ SHAWMUT, STT2240SPG-CN,

STT2BL240SPG-CN rated 120/240Vac, (In=20kA).

Maximum distance between installation and

reduction is 5m.