7.1.13 Serial line terminations

To set the serial line terminations operate on DIP

1.
The board has two DIP switches used to configure the

serial line terminations (120 Ohm) (Tab. 7, page 25).
Every peripheral that is situated at the end of a line

must be terminated using the appropriate dip-switch

in order to prevent signal reflection and distortion.

SERIAL LINE TERMINATIONS (DIP 1)

Description

SW 1-2-3-4-5-6

SW 7

SW 8

Configur

ation

Serial line

terminations

ON RS-485-2 line, termination

enabled

OFF RS-485-2 line, termination

disabled

ON –

RS-485-1 line, termination

enabled

OFF –

RS-485-1 line, termination

disabled

Tab. 7

7.1.14 Protocol configuration

To set the protocol operate on DIP 3.
Video positioning systems of the P&T can be

controlled by a range of protocols.

PROTOCOL CONFIGURATION (DIP 3)

SW 1 SW 2 SW 3 SW 4 Configuration
ON

OFF

ON

OFF

PANASONIC

OFF

OFF

ON

OFF

ERNITEC

OFF

ON

OFF

OFF

SENSORMATIC

ON

OFF

OFF

OFF

PELCO D

OFF

OFF

OFF

OFF

VIDEOTEC MACRO

OFF

ON

ON

OFF

NETWORK

Tab. 8

7.1.15 Address configuration

To set the address operate on DIP 2.
It is possible to set the pan & tilt address: from 1 to

1023. Binary code is used to select the address, using

the dip-switches (A Appendix - Address table, page 

70).