Installation, 3 control terminals, English 2 – AC International Lenze SV01B User Manual
Page 13
ENGLISH
2
Installation
3.2.3
Control terminals
Terminal Data for control connections
1
Digital Input: Start/Stop
input resistance = 4.k
Ω
2
Analog Common
5
Analog Input: 0...0 VDC
input resistance: >50 k
Ω
6
Internal DC supply for speed pot
+0 VDC, max. 0 mA
25
Analog Input: 4...20 mA
input resistance: 250
Ω
4
Digital Reference/Common
+5 VDC / 0 VDC, depending on assertion level
11
Internal DC supply for external devices
+2 VDC, max. 50 mA
13A
Digital Input: Configurable with P2
input resistance = 4.k
Ω
13B
Digital Input: Configurable with P22
13C
Digital Input: Configurable with P2
14
Digital Output: Configurable with P42
DC 24 V / 50 mA; NPN
30
Analog Output: Configurable with P50…P55
0…0 VDC, max. 20 mA
16
Relay output: Configurable with P40
AC 250 V / A
DC 24 V / 2 A … 240 V / 0.22 A, non-inductive
17
6 25 4 11 13A13B13C
17
5
1 2
14 30 16
AOUT
DIGOUT
2k … 10k
+10 V
AIN
AIN
COM
COM
ALsw
25
2
4 … 20 mA
5
2
0 … 10 V
0 … 5 V
1 2 4 13A 13B 13C
+12 VDC - 0 %
…
+30 VDC + 0 %
ALsw
+15V
1 2 4 13A 13B 13C
ALsw
COM
PNP
NPN
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
V009
Assertion level of digital inputs
The digital inputs can be configured for active-high or active-low by setting the Assertion Level
Switch (ALsw) and P20. If wiring to the drive inputs with dry contacts or with PNP solid state
switches, set the switch and P20 to “High” (+). If using NPN devices for inputs, set both to “Low”
(-). Active-high (+) is the default setting.
HIGH = +2 … +0 V
LOW = 0 … + V
Note
An
fault will occur if the Assertion Level switch (ALsw) position does not match the
parameter P20 setting and P00 or any of the digital inputs (P2...P2) is set to a
value other than 0.