2

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

Slip
Compensation

0.0

0.0

{%}

0.0

Increase P70 until the motor speed no
longer changes between no load and
full load conditions.

()

Current Limit

200

0

{%}

CLim

max

• When the limit is reached, the

drive displays , and either the
acceleration time increases or the
output frequency decreases.

• Digital outputs can also indicate

when the limit is reached; see P40,
P42.

• Refer to section 2.2 for CLim

max

DC Brake
Voltage

0.0

0.0

{%}

0.0

Setting is a percent of the nominal DC
bus voltage.

DC Brake Time

0.0

0.0

{s}

999.9

Note

CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING

DC Brake voltage (P74) is applied for the time specified by P75 with the
following exceptions:
• If P=,  and P75=999.9 the brake voltage will be applied

continuously until a run or fault condition occurs.

• If P0=2, 4… and P75=999.9, brake voltage will be applied for 5s
• If P2…P2=8 and the corresponding TB- input is CLOSED,

brake voltage will be applied until the TB- input is OPENED or a fault
condition occurs.

Display
Frequency
Multiplier

0.00

0.00

50.00

• Allows frequency display to be

scaled

• P78 = 0.00: Scaling disabled
• P78 > 0.00: Display = Actual

Frequency X P78

Example: If P78 = 29.7 and actual frequency = 0 Hz,

Drive displays 750 (rpm)

Run Screen
Display

0

0 {Parameter Number}

599 • 0 = Normal Run Screen, this display

depends on mode of operation.
See Section 4.2.

• Other selections choose a diagnostic

parameter to display (P50…P599).

Skip frequency 

0.0

0.0

{Hz}

500

• Drive will not run in the defined skip

range; used to skip over frequencies
that cause mechanical vibration

• P8 and P82 define the start of

the skip ranges

• P84 > 0 defines the bandwidth of

both ranges.

Skip frequency 2

0.0

0.0

{Hz}

500

Skip frequency
bandwidth

0.0

0.0

{Hz}

0.0

Note
Bandwidth (Hz) = f

s

(Hz) + P84 (Hz) f

s

= P8 or P82

Example: P8 = 8 Hz and P84 = 4 Hz; skip range is from 8 to 22 Hz

() Any changes to this parameter will not take effect until the drive is stopped