Commissioning, 5 vector parameters, English 27 – AC International Lenze SV01B User Manual

Page 28

Advertising
background image

ENGLISH

27

Commissioning

4.5.5

Vector Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

()

Drive Mode

0

0 Constant V/Hz

Constant torque V/Hz control for
general applications

 Variable V/Hz

Variable torque V/Hz control for
centrifugal pump and fan applications

2 Enhanced Constant V/Hz

For single or multiple motor
applications that require better
performance than settings 0 or , but
cannot use Vector mode, due to:
• Missing required motor data
• Vector mode causing unstable motor

operation

 Enhanced Variable V/Hz

4 Vector Speed

For single-motor applications requiring
higher starting torque and speed
regulation

5 Vector Torque

For single-motor applications requiring
torque control independent of speed

Note
To configure the drive for either Vector mode or Enhanced V/Hz mode:
• P00 = 4, 5:
- Set P02...P0 according to motor nameplate
- Set P99 = 
- Make sure motor is cold (20° - 25° C) and apply a Start command
- Display will indicate

for about 40 seconds

- Once the calibration is complete, the display will indicate

; apply

another Start command to actually start the motor

- If an attempt is made to start the drive in Vector or Enhanced V/Hz

mode before performing the Motor Calibration, the drive will display

and will not operate

• P00 = 2, : Same as above but only need to set P02…P04

()

Motor Rated
Voltage

0

{V}

00

• Default setting = drive rating
• Set to motor nameplate data

()

Motor Rated
Current

0.0

{A}

500.0

()

Motor Rated
Frequency

0

0

{Hz}

000

Set to motor nameplate data

()

Motor Rated
Speed

750 00

{RPM}

5000

()

Motor Cosine Phi

0.80

0.40

0.99

Note
If motor cosine phi is not known, use one of the following formulas:
cos phi = motor Watts / (motor efficiency X P02 X P0 X .72)
cos phi = cos [ sin



(magnetizing current / motor current) ]

() Any changes to this parameter will not take effect until the drive is stopped