Troubleshooting and diagnostics, 2 drive configuration messages – AC International Lenze SV01B User Manual

Page 33

Advertising
background image

ENGLISH

2

Troubleshooting and Diagnostics

Status / Warning

Cause

Remedy

PID Mode Active

Drive has been put into PID
Mode. See P200.

Sleep Mode is active

See P240...P242

Start Pending

The drive has tripped into a fault
and will automatically restart
(P0 = ...)

To disable Auto-Restart, set
P0 = 0...2

PID Mode disabled.

Drive has been taken out of PID
Mode. See P200.

Output frequency = 0 Hz
(outputs U, V, W inhibited)

Stop has been commanded from
the keypad, terminal strip, or
network

Apply Start command (Start
Control source depends on
P00)

5.2

Drive Configuration Messages

When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that indicates
how the drive is configured. If the drive is in a Stop state when this is done, the display will also
indicate which control source commanded the drive to Stop
(the two displays will alternate every second).

Configuration Display

Format = x.y.zz x = Control Source:

= Local Keypad
= Terminal Strip
= Remote Keypad
= Network

y = Mode:

= Speed mode
= PID mode
= Vector Torque mode

zz = Reference:

= Keypad s t
= 0-0 VDC (TB-5)
= 4-20 mA (TB-25)
= Jog
= Network
= MOP

= Preset ...7

Example:

= Local Keypad Start control, Speed mode, Keypad speed reference

= Terminal Strip Start control, PID mode, 0-0 VDC setpoint reference

= Network Start control, Vector Torque mode, Preset Torque #2 reference

Stop Source Display

Format = x

= Stop command came from Local Keypad
= Stop command came from Terminal Strip
= Stop command came from Remote Keypad
= Stop command came from Network