Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

Minimum Alarm

0.0

P204

P205

Use with P40, P42 = 8...2

Maximum Alarm

0.0

P204

P205

Preset PID
Setpoint #

0.0

P204

P205

TB-A activated; P2 =  and
P200 =  or 2

Preset PID
Setpoint #2

0.0

P204

P205

TB-B activated; P22 =  and
P200 =  or 2

Preset PID
Setpoint #

0.0

P204

P205

TB-C activated; P2 =  and
P200 =  or 2

Sleep Threshold

0.0

0.0

{Hz}

500.0

• If drive speed < P240 for longer than

P24, output frequency = 0.0 Hz;
drive display =

• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again

when speed command is above
P240

• P242 > 0.0: Drive will restart when

the PID feedback differs from the
setpoint by more than the value
of P242

or

when the PID loop

requires a speed above P240.

Sleep Delay

0.0

0.0

{s}

00.0

Sleep Bandwidth

0.0

0.0

B

max

Where: B

max

= |(P205 - P204)|