Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

Start Method

0

0 Normal
 Start on Power-up

Drive will automatically start when
power is applied.

2 Start with DC Brake

When start command is applied, drive
will apply DC braking according to
P74, P75 prior to starting the motor

 Auto Restart

Drive will automatically restart after
faults, or when power is applied.

4 Auto Restart with DC Brake

Combines settings 2 and 

5 Flying Start/Restart #

• Drive will automatically restart after

faults, or when power is applied.

• After  failed attempts, drive will

Auto Restart with DC brake.

• P0 = 5: Performs speed search,

starting at Max Frequency (P0)

• P0 = : Performs speed search,

starting at the last output frequency
prior to faulting or power loss

• If P = 0, a flying START is

performed when a start command is
applied.

 Flying Start/Restart #2

Note
• P0 = 0, 2: Start command must be applied at least 2 seconds after

power-up;

fault will occur if start command is applied too soon.

• P0 = , …: For automatic start/restart, the start source must be

the terminal strip and the start command must be present.

• P0 = 2, 4…: If P75=999.9, dc braking will be applied for 5s.
• P0 = …: Drive will attempt 5 restarts; if all restart attempts fail,

drive displays (fault lockout) and requires manual reset.

• P0 = 5, : If drive cannot catch the spinning motor, drive will trip into

. fault.

WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic
starting/restarting should only be used on equipment that is inaccessible to personnel.
Stop Method

0

0 Coast

Drive’s output will shut off immediately
upon a stop command, allowing the
motor to coast to a stop

 Coast with DC Brake

The drive’s output will shut off and then
the DC Brake will activate (see P74,
P75)

2 Ramp

The drive will ramp the motor to a stop
according to P05 or P2.

 Ramp with DC Brake

The drive will ramp the motor to 0 Hz
and then the DC Brake will activate
(see P74, P75)

Rotation

0

0 Forward Only

If PID mode is enabled, reverse
direction is disabled (except for Jog).

 Forward and Reverse