ENGLISH



Troubleshooting and Diagnostics

5

Troubleshooting and Diagnostics

5.1

Status/Warning Messages

Status / Warning

Cause

Remedy

DC-injection brake active

DC-injection brake activated
• activation of digital input

(P2...P2 = 8)

• automatically (P0 = 2, 4...)
• automatically (P = , )

Deactivate DC-injection brake
• deactivate digital input

• automatically after P75 time

has expired

Drive ID warning

The Drive ID (P502) stored on
the EPM does not match the
drive model.

• Verify motor data

(P02…P0) and perform
Auto Calibration.

• Set drive mode (P00) to 0 or 
• Reset the drive (P99 to  or 4)

and reprogram.

Motor Auto-calibration is being
performed

See P00, P99

An EPM that contains valid data
from a previous software version
has been installed

An attempt was made to change
parameter settings

Parameter settings can only be
changed after the EPM data is
converted to the current version
(P99 = 5)

Current Limit (P7) reached

Motor overload

• Increase P7
• Verify drive/motor are proper

size for application

Decel Override

The drive has stopped
decelerating to avoid tripping into

fault, due to excessive motor

regen (2 sec max).

If drive trips into fault:
• Increase P05, P2
• Install Dynamic Braking option

Error

Invalid data was entered, or an
invalid command was attempted

Fast Current Limit

Overload

Verify drive/motor are proper size
for application

Flying Restart Attempt after Fault P0 = 5,

OEM Settings Operation warning An attempt was made to change

parameter settings while the
drive is operating in OEM
Settings mode (P99 = )

In OEM Settings mode, making
changes to parameters is not
permitted

OEM Defaults data warning

An attempt was made to use
(or reset to) the OEM default
settings (P99 =  or 2) using an
EPM without valid OEM data.

Install an EPM containing valid
OEM Defaults data

Fault Lockout

The drive attempted 5 restarts
after a fault but all attempts were
unsuccessful (P0 = ...)

• Drive requires manual reset
• Check Fault History (P500)

and correct fault condition

PID Deceleration Status

PID setpoint has finished
its ramp but the drive is still
decelerating to a stop.