Commissioning, English 20 – AC International Lenze SV01B User Manual

Page 21

Advertising
background image

ENGLISH

20

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

Relay Output
TB-, 7

0

0 None

Disables the output

 Run

Energizes when the drive is running

2 Reverse

Energizes when reverse rotation is active

 Fault

De-energizes when the drive trips, or
power is removed

4 Inverse Fault

Energizes when the drive trips

5 Fault Lockout

P0 = ...: De-energizes if all restart
attempts fail

 At Speed

Energizes when output frequency =
commanded frequency

7 Above Preset Speed #

Energizes when output freq. > P

8 Current Limit

Energizes when motor current = P7

9 Follower Loss (4-20 mA)

Energizes when 4-20 mA signal falls
below 2 mA

0 Loss of Load

Energizes when motor load drops
below P45; see also P4

 Local Keypad Control Active

Energizes when the selected source is
active for start control

2 Terminal Strip Control Active
 Remote Keypad Control Active
4 Network Control Active
5 Standard Reference Active

Energizes when P0 reference is active

 Auto Reference Active

Energizes when Auto Reference
is activated using TB- input; see
P2...P2

7 Sleep Mode Active

See P240...P242

8 PID Feedback < Min. Alarm

Energizes when PID feedback signal
< P24

9 Inverse PID Feedback < Min.

Alarm

De-energizes when PID feedback
signal < P24

20 PID Feedback > Max Alarm

Energizes when PID feedback
signal > P25

2 Inverse PID Feedback > Max

Alarm

De-energizes when PID feedback
signal > P25

22 PID Feedback within

Min/Max Alarm range

Energizes when PID feedback signal
is within the Min/Max Alarm range; see
P24, P25

2 PID Feedback outside

Min/Max Alarm range

Energizes when PID feedback signal is
outside the Min/Max Alarm range; see
P24, P25

24 Reserved
25 Network Activated

Requires optional communication
module (refer to the network module
documentation).