Commissioning, English 28 – AC International Lenze SV01B User Manual

Page 29

Advertising
background image

ENGLISH

28

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

()

Motor Stator
Resistance

0.00

0.00

{

W}

4.00

• Will be automatically programmed by

P99

• Changing these settings can

adversely affect performance.
Contact factory technical support
prior to changing

()

Motor Stator
Inductance

0.0

0.0

{mH}

2000

Torque Limit

00

0

{%}

400

When P00 = 5, sets the maximum
output torque.

Preset Torque
Setpoint #

00

0

{%}

400

TB-A activated; P2 =  and
P00 = 5

Preset Torque
Setpoint #2

00

0

{%}

400

TB-B activated; P22 =  and
P00 = 5

Preset Torque
Setpoint #

00

0

{%}

400

TB-C activated; P2 =  and
P00 = 5

()

Current Loop P
Gain

0.25

0.00

.0

Changing these settings can adversely
affect performance. Contact factory
technical support prior to changing.

()

Current Loop I
Gain

5

2

{ms}

9990

()

Speed Loop
Adjustment

0.0

0.0

{%}

20.0

Motor Auto-
calibration

0

0 Calibration Not Done

• If P00 = 2...5, motor calibration

must be performed, but motor data
must be programmed first

• An alternating

/

will occur if:

- motor calibration is attempted with

P00 = 0 or 

- motor calibration is attempted

before programming motor data

 Calibration Enabled

2 Calibration Complete

Note
To run the Auto Calibration:
- Set P02...P0 according to motor nameplate
- Set P99 = 
- Make sure motor is cold (20° - 25° C)
- Apply a Start command
- Display will indicate

for about 40 seconds

- Once the calibration is complete, the display will indicate

; apply

another Start command to actually start the motor

- Parameter P99 will now be set to 2.

() Any changes to this parameter will not take effect until the drive is stopped