INSTALLATION

1.

Mount the Current Transformer (CT), if supplied, in an area that is convenient to loop one of the motor leads
through it, usually the motor starter enclosure.

2.

Loop one of the motor leads through the CT the number of turns specified in Table I.

3.

Mount the Terminal Socket at desired location.

4.

Connect wiring (Not Supplied) per wiring Diagram I for use with no Current Transformer and per wiring
Diagram II for use with a Current Transformer.

5.

Plug Motor into Terminal Socket.

SETTINGS

1.

To protect against dry running, set Current Adjuster to a current value midway between full load operating
current (INFO) and no load motor current (INL).

NOTE: The minimum current setting shown in Table I corresponds to "I" on the Current Adjuster Dial.
Each setting on the dial is a multiple of the minimum setting.

2.

To protect against Low Flow Operation, operate pump at desired flow and slowly increase setting on Current
Adjuster until pump shuts off.

3.

Set time delay from .1 to 5 seconds as desired. Delay is used to prevent nuisance tripping that occurs from
variations in line voltage.

3296 M Group 6/05