Specifications – Goulds Pumps 3296M - IOM User Manual

Page 85

Advertising
background image

3296 M Group 6/05

81

SPECIFICATIONS

GTP Controller and AC Current Transformer - Keytron, Inc., Model K1000

Input Power . . . . . . . . . . . . . . . . . . . . 120/240 VAC, 50/60 Hz, 6 VA
AC Current Sense Range. . . . . . . . . . . . . . 0.2 to 20, 2 to 200 and 20 to 300 Amp
Type AC Current Sensor . . . . . . . . . . . . . . Toroidal transformer
AC Current Adjustments . . . . . . . . . . . . . . Overcurrent and undercurrent setpoint

AC Sense Accuracy . . . . . . . . . . . . . . . .

± 3% (proportional and fixed errors).

Temperature Input interference . . . . . . . . . . Switchbale between thermocouple and RTD

Temperature Control . . . . . . . . . . . . . . . . Setpoint.
Temperature Display Range . . . . . . . . . . . . 0° to 2000°C. Actual range depends on type sensor used.
4 to 20 mA Display Range . . . . . . . . . . . . . 0-1, 0 to 10, 0 to 100.
4 to 20 mA Controls . . . . . . . . . . . . . . . . Set point and Span.
Auxiliary Inputs (2) . . . . . . . . . . . . . . . . Momentary opening of sensor switch contacts

will trigger and set latch.

Switches . . . . . . . . . . . . . . . . . . . . . .

a.

120/240 AC Line Select

. . . . . . . . . . . . . . . . . . . . . . . . . . .

b.

AC Current Range

. . . . . . . . . . . . . . . . . . . . . . . . . . .

c.

Therm/RED Select

. . . . . . . . . . . . . . . . . . . . . . . . . . .

d.

4-20 mA Meter Decimal Select.

. . . . . . . . . . . . . . . . . . . . . . . . . . .

e.

Hi/Lo AC Threshold Select.

. . . . . . . . . . . . . . . . . . . . . . . . . . .

f.

Relay OFF/ON.

. . . . . . . . . . . . . . . . . . . . . . . . . . .

g.

Auto Reset OFF/ON.

Alarm & Control Relay Contacts . . . . . . . . .

NC, 5.0 amps resistive, 240 VAC.

Alarm Circuit. . . . . . . . . . . . . . . . . . . . Alarm relay contacts will open if AC power to the K1000 or

internal supply fails

Start Delay . . . . . . . . . . . . . . . . . . . . . 10 Seconds (for inrush current)
DC Supply for External Sensors . . . . . . . . . . 15 Volts DC, 50 ma regulated
Reset . . . . . . . . . . . . . . . . . . . . . . . . Front panel pushbutton switch, or remotely from K1000

terminal block.

Auto-Reset . . . . . . . . . . . . . . . . . . . . . Selectable, effective on undercurrent mode only. One minute

delay.

Panel Meter . . . . . . . . . . . . . . . . . . . . 3 ½ digit LCD type meter
Indicators . . . . . . . . . . . . . . . . . . . . . . 6 LED red status indicators, which flash in the on state, and

one green AC Line indicator.

Enclosure . . . . . . . . . . . . . . . . . . . . . . Molded polyester fiberglass, NEMA-4X UL and CSA

approved.

Enclosure Size and Mounting Dim. . . . . . . . . 6" x 6" x 4", 6.94" x 4.00"
Line Protection . . . . . . . . . . . . . . . . . . . Transient suppressor
Operating Temperature Range . . . . . . . . . . . -25 to +55° C.
Leak Detection Pressure Switch -

NEMA 4 - Custom Control Sensors, Inc., Model G 8001, REF Instruction D.
NEMA 7 - Custom Control Sensors, Inc., Model 611GCE1, REF Instruction E.

Vibration Transmitter

NEMA 4 - Balmac, Inc., Model 191, REF Instruction F.

Advertising