Preventive measures – Hale Q Series Muscle User Manual

Page 196

Advertising
background image

Cavitation

196

MUSCLE (Midship) Pumps Installation, Operation, and Maintenance Manual

p/n: 029-0020-63-0

Monitor barometric pressure. NFPA standard sets a baseline of 29.9” Hg. (See
Table G-3: “Lift Loss from Barometric Reading.”)

Regularly inspect suction hoses to check for air leaks. Air leaks can also cause
cavitation.

Check suction strainer for blockage or effectiveness. See heading “Strainers” on
page 197.

Preventive Measures

Consider the size of the suction hose. Table G-4: “Hose Size vs. Pump Rating
Capacity” on page 196, lists the
NFPA pre-selected hose sizes for each pump-rat-
ing capacity. Using the appropriately sized hose minimizes the occurrence of cav-
itation. An undersized suction hose can lead to cavitation.

Consider the piping within the truck. Suction losses can result from additional suc-
tion piping added to the fire pump during assembly.

Table G-3: Lift Loss from Barometric Reading

Barometric

Reading

in. (mb)

Lift Loss, Head

Ft. (Meters)

29.9

(1,012.5)

NFPA Base Line - 2.38 ft. (0.73 m)

29.7

(1,005.8)

0.2

(0.6)

29.5

(999)

0.5

(0.15)

29.3

(999.2)

0.7

(0.21)

29.1

(985.4)

0.9

(0.27)

28.9

(987.7)

1.1

(0.33)

28.7

(971.9)

1.4

(0.43)

Table G-4: Hose Size vs. Pump Rating Capacity (Sheet 1 of 2)

Hose Diameter

in. (mm)

3”

(75)

4”

(100)

4.5”

(110)

5”

(125)

6”

(150)

Dual

6” (150)

Triple

6” (150)

Flow - gpm (lpm)

Lift Loss gpm (lpm)

250 (1,000)

5.2 (1.6)

350 (1,300)

2.5 (0.7)

500 (2,000)

5.0 (1.5)

3.6 (1.5)

750 (3,000)

11.4 (3.5)

8.0 (3.5)

4.7 (1.4

1.9 (0.6)

1,000 (4,000)

14.5 (4.4)

8.4 (2.6)

3.4 (1.0)

1,250 (5,000)

13.0 (4.0)

5.2 (1.6)

1,500 (6,000)

7.6 (2.3)

1.9 (0.6)

1,750 (7,000)

2.6 (0.8)

2,000 (8,000)

3.4 (13)