Recommended “annual” procedures – Hale Q Series Muscle User Manual

Page 72

Advertising
background image

92

MUSCLE (Midship) Pumps Installation, Operation, and Maintenance Manual

p/n: 029-0020-63-0

RECOMMENDED “ANNUAL” PROCEDURES

Complete all previous checks on all questions.

Check gauge calibration - see page 75.

Check oil level in AutoLube

®

assembly (SAE-EP 90 or 80W-90); see operation

and maintenance manual for details.

Lubricate power transfer cylinder, power shift cylinder, and shift control valve
with vacuum cylinder oil, if applicable.

Change pump gearbox oil and refill (SAE-EP 90 oil or 80W-90).

Check individual drain lines from pump to multi-drain to ensure proper drainage
and protection from freezing.

Lubricate transfer valve mechanism on two stage pumps. Dry moly spray is pre-
ferred.

Disassemble priming pump and clean vanes.

Run yearly standard pump test (per NFPA-1911) to check pump performance
levels – chart provided below.

Repacking of pump is recommended every two or three years.

Note: The preceding general recommendations are provided for normal use and condi-
tions. Extreme conditions or variables may indicate a need for increased maintenance.
Good preventative maintenance lengthens pump life, ensures greater dependability, and
minimizes downtime. See “Muscle Pump Service Chart, Part 1 of 3” on page 88.

Annual pump Test Results, in PSIG (kPa)

Category

Capacity at 150

(1000)

Capacity at 200

(1400)

Capacity at 250

(1700)

Hose Layout

Nozzle Size

Nozzle Pressure

Gallons (Liters) per Minute

Pump Pressure, Current Engine Speed

Engine Speed from Original Test
Documents

Lift and Suction Hose Size and
Number.

Advertising
This manual is related to the following products:

8FG