4.3.5.2.7 Program Parameter Indicators

Table 4-1

is also useful for the range and limits set by the Setup Tool software

and the optional Monitorware communications software.

Table 4-1 Composer Parameters Range and Type

Allowed Entries

Parameter

Min

Max

Default

Type

Format

Concentration Target

0.0

100.0

5.0000

Float

xxx.xxxx

Process Gain

0.0001

999.9999

18.7000

Float

xxx.xxxx

Dead Time

0.01

1000.00

1.80

Float

xxxx.xx

Time Constant

0.01

1000.00

7.73

Float

xxxx.xx

Relay Limit

0.0

100.000

0.100

Float

xxx.xxx

Fuzzy

No

Yes

No

Cell Temperature

0.1

65.0

30.0

Float

xx.x

Carrier Molecular Weight

1.000

1000.00

2.01600

Float

xxxx.xxx

Carrier Gamma

1.0

2.0

1.404

Float

x.xxxxx

Precursor Molecular Weight

1.000

1000.00

28.01000

Float

xxxx.xxx

Precursor Gamma

1.0

2.0

1.399

Float

x.xxxxx

Bubbler Range

0

5000

200

Integer xxxx

Bubbler Max Flow

0

2000

200

Integer xxxx

Dilution Range

0

5000

2000

Integer xxxx

Dilution Max Flow

0

2000

800

Integer xxxx

Total Channel Flow

0

2000

200

Integer xxxx

Bubbler Minimum Flow

0

2000

0

Float

xxxx.x

Control Input Range Max

0

100.0000

50.0000

Float

xxx.xxxx

Control Input Range Min

0

100.0

0.0

Float

xxx.xxxx