28
9L
Composer Operating Manual
4.3.5.2.7 Program Parameter Indicators
is also useful for the range and limits set by the Setup Tool software
and the optional Monitorware communications software.
Table 4-1 Composer Parameters Range and Type
Allowed Entries
Parameter
Min
Max
Default
Type
Format
Concentration Target
0.0
100.0
5.0000
Float
xxx.xxxx
Process Gain
0.0001
999.9999
18.7000
Float
xxx.xxxx
Dead Time
0.01
1000.00
1.80
Float
xxxx.xx
Time Constant
0.01
1000.00
7.73
Float
xxxx.xx
Relay Limit
0.0
100.000
0.100
Float
xxx.xxx
Fuzzy
No
Yes
No
Cell Temperature
0.1
65.0
30.0
Float
xx.x
Carrier Molecular Weight
1.000
1000.00
2.01600
Float
xxxx.xxx
Carrier Gamma
1.0
2.0
1.404
Float
x.xxxxx
Precursor Molecular Weight
1.000
1000.00
28.01000
Float
xxxx.xxx
Precursor Gamma
1.0
2.0
1.399
Float
x.xxxxx
Bubbler Range
0
5000
200
Integer xxxx
Bubbler Max Flow
0
2000
200
Integer xxxx
Dilution Range
0
5000
2000
Integer xxxx
Dilution Max Flow
0
2000
800
Integer xxxx
Total Channel Flow
0
2000
200
Integer xxxx
Bubbler Minimum Flow
0
2000
0
Float
xxxx.x
Control Input Range Max
0
100.0000
50.0000
Float
xxx.xxxx
Control Input Range Min
0
100.0
0.0
Float
xxx.xxxx