3.1.13.5 Programming the Controller’s Parameters (Bulk Flow)

When operating in the “Bulk Flow Control” configuration, the following list of
parameters must be entered. See

section 4.3.5.2.7 on page 4-15

for a complete

description of each parameter and

section 4.3.5.3 on page 4-17

(all sections)

for a description of the display’s operation.

3.1.13.5.1 List of Parameters used for Describing the Bulk Flow

Control Configuration

PROG # . . . . . . . . . . . . . . . . . . . . . Numerical indication of program number

(1-9).

Concentration Target . . . . . . . . . . . Parameter that is used by the Composer to

internally multiply the CF setpoint (as read
by the composer on the Control In
connector) and thereby form the Bulk Flow
Target. See

section 3.1.13.6 on page 3-18

for help in setting this parameter. (0.000 to
100.00%)

Process Gain . . . . . . . . . . . . . . . . . Set parameter’s value per

section

3.1.13.6.1 on page 3-18

.

Dead Time . . . . . . . . . . . . . . . . . . . Initially set to 2 seconds, do not set less

than 1.0 second. Actual time will depend on
delays in MFC read-back.

Time Constant . . . . . . . . . . . . . . . . Set to 1 second

Relay Limit. . . . . . . . . . . . . . . . . . . Units are sccm in Bulk flow configuration

Fuzzy Y/N

Cell Temperature

Carrier MW

Carrier

γ

Precursor MW

Precursor

γ

MFC Range, Bubbler

Max Flow Bubbler