3.2.1.2 Tuning a Fast Delivery System
If the source response has been characterized as fast (Dead Time is less than
1 second), set the INTEGRATING TYPE control parameters as follows:
DEAD TIME . . . . . . . . . . . . . . . . . since this is a fast source, set this
parameter’s value to 0.1 and leave it there.
TIME CONSTANT. . . . . . . . . . . . . set this parameter’s value to 0.1 and leave
it there.
PROCESS GAIN . . . . . . . . . . . . . approximate the process gain by dividing
the increase in concentration (%) by the
increase in Bubbler flow rate (sccm). Set
this parameter to this computed value.
Optimize this value by changing the value
in use. Remember that increasing the
value of this parameter reduces the
controller change for a given error in the
measured concentration. That is, the
system responds more slowly with higher
values of process gain.
NOTE: If satisfactory control cannot be established using only PROCESS
GAIN the system is probably not a fast system.