Electrical installation, Stop – Lenze ECSCx Axis cold plate User Manual

Page 101

Advertising
background image

Electrical installation

Power terminals

5

l

101

EDKCSCX064 DE/EN/FR 4.0

(

Stop!

No device protection if the mains voltage is too high

The mains input is not internally fused.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the maximally permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.

ƒ

All power connections are plug connections and coded. The ECSZA000X0B
plug connector set must be ordered separately.

ƒ

Installation of the cables to EN 60204−1.

ƒ

The cables used must comply with the approvals required at the site of
use (e.g. VDE, UL, etc.).

Assignment of the plug connectors

Plug
connector/termi
nal

Function

Electrical data

X23

DC−bus voltage connection

X23/+UG

Positive DC−bus voltage

Dependent on application and
type
0 ... 770 V
2 ... 24.5 A (

^

91)

X23/+UG

X23/−UG

Negative DC−bus voltage

X23/−UG

X23/PE

Earth connection

X23/PE

X24

Motor connection

X24/U

Motor phase U

Dependent on application and
type
0 ... 480 V
1.6 ... 20 A (

^

91)

X24/V

Motor phase V

X24/W

Motor phase W

X24/PE

Earth connection

X25

Motor holding brake connection

X25/BD1

Brake connection +

23 ... 30 V DC,
max. 1.5 A

X25/BD2

Brake connection −