Mounting steps – Lenze ECSCx Axis cold plate User Manual

Page 96

Advertising
background image

Mechanical installation

Mounting in cold−plate design
Mounting steps

4

l

96

EDKCSCX064 DE/EN/FR 4.0

4.2.2

Mounting steps

А

Б

В

ECSXA030

Fig. 4−2

Mounting for "cold−plate design"

Proceed as follows to mount the axis module:
1. Prepare the fixing holes on the mounting plate.

Use a drilling jig for this purpose.

2. Clean and degrease the contact area of collective cooler and heatsink of

the axis module (e.g. with methylated spirit).

3. Screw the support onto the collective cooler.
4. Insert the axis module from above

 into the support ‚ and fasten the

two stud bolts with 3.5 ... 4.5 Nm

ƒ.

)

Note!

Penetration depth of the screws into the collective cooler:
approx. 15 mm!

I

Tip!

The heat transfer resistance is reduced if − following step 2. −

ƒ

a thin layer of heat conducting paste is applied to the contact
surface or

ƒ

heat conducting foil is used.