Electrical installation

Installation according to EMC (installation of a CE−typical drive system)

5

l

99

EDKCSCX064 DE/EN/FR 4.0

Shielding

ƒ

Connect the motor cable shield to the axis module

–

with the ECSZS000X0B shield mounting kit.

–

extensively to the mounting plate below the axis module.

–

Recommendation: For the shield connection, use earthing clamps on
bare metal mounting surfaces.

ƒ

If contactors, motor protection switches or terminals are located in the
motor cable:

–

Connect the shields of the connected cables to each other and connect
them to the mounting plate, too, with a surface as large as possible.

ƒ

Connect the shield in the motor terminal box or on the motor housing
extensively to PE:

–

Metal glands at the motor terminal box ensure an extensive connection
of the shield and the motor housing.

ƒ

Shield UG cables and control cables from a length of 0.3 m:

–

Connect both shields of the digital control cables.

–

Connect one shield end of the analog control cables.

–

Always connect the shields to the shield connection at the axis module
over the shortest possible distance.

ƒ

Use of the ECS modules in residential areas:

–

Additionally dampen the shield in order to limit the interfering
radiation:

³10 dB . This can be achieved by using standard, closed,

metallic, and earthed control cabinets or boxes.

Earthing

ƒ

Earth all metallically conductive components (e.g. ECS modules, RFI filters,
motor filters, mains chokes) using suitable cables connected to a central
earthing point (PE rail).

ƒ

Maintain the minimum cross−sections prescribed in the safety
regulations:

–

For EMC not the cable cross−section is important, but the surface of the
cable and the contact with a cross−section as large as possible, i.e. large
surface.