Resolver connection, Electrical installation – Lenze ECSCx Axis cold plate User Manual

Page 128

Advertising
background image

Electrical installation

Wiring of the feedback system
Resolver connection

5

l

128

EDKCSCX064 DE/EN/FR 4.0

5.5.1

Resolver connection

)

Note!

ƒ

Use the prefabricated Lenze system cables for the connection of
a resolver.

ƒ

Cable length: max. 50 m

ƒ

Depending on the cable length and resolver used parameterise
the code C0416 (resolver excitation amplitude).
Check the resolver control with code C0414 (recommended
values: 0.5 ... 1.2; ideal value: 1.0).

ƒ

Before using a resolver from another manufacturer, please
consult Lenze.

Connect a resolver via the 9−pole Sub−D socket X7.

Features

ƒ

Resolver: U = 10 V, f = 4 kHz

ƒ

Resolver and resolver supply cable are monitored for open circuit (fault
message "Sd2").

+REF

-REF

+COS

-COS

+SIN

-SIN

R1 (+KTY)

R2 (-KTY)

KTY

1

2
3
4
5
6
7
8
9

X7

0.14

26

0.5

20

mm

2

AWG

Æ

1

5

6

9

X7

ECSXA022

Fig. 5−12

Resolver connection

Assignment of socket connector X7: Sub−D 9−pole

Pin

1

2

3

4

5

6

7

8

9

Signal

+Ref

−Ref

GND

+COS

−COS

+SIN

−SIN

R1

(+KTY)

R2

(−KTY)

0.5 mm

2

(AWG 20)

˘

0.14 mm

2

(AWG 26)

Advertising