Electrical installation

Wiring of the feedback system
Encoder connection

5

l

130

EDKCSCX064 DE/EN/FR 4.0

Via the 9−pole Sub−D−plug X8, you can connect the following encoders:

ƒ

Incremental encoder (TTL encoder)

with two 5 V complementary signals (RS−422) that are electrically
shifted by 90°.

with zero track that can be connected optionally.

ƒ

Sin/cos encoder (singleturn or multiturn rotary transducer)

with supply voltage (5 ... 8 V).

with serial communication.
The initialisation time of the axis module is extended to approx. 2 s.

The controller supplies the encoder with voltage.
Use C0421 to set the supply voltage V

CC

(5 ... 8 V) to compensate, if required, the

voltage drop [

DV] on the encoder cable:

DU ^ 2 @ L

L

[m]

@ Rńm [Wńm] @ I

G

[A]

DV

Voltage drop on the encoder cable [V]

L

L

Cable length [m]

R/m

Ohmic resistance per meter of cable length [

W/m]

I

G

Encoder current [A]

(

Stop!

Observe the permissible supply voltage of the encoder used. If the
values in C0421 are set too high, the encoder can be destroyed!