Safety instructions

Thermal motor monitoring

Forced ventilated or naturally ventilated motors

2

l

81

EDKCSCX064 DE/EN/FR 4.0

2.2.1

Forced ventilated or naturally ventilated motors

Parameter setting
The following codes can be set for I

2

x t monitoring:

Code

Meaning

Value range

Lenze setting

C0066

Display of the I

2

x t load of the motor

0 ... 250 %

C0120

Threshold: Triggering of error "OC6"

0 ... 120 %

0 %

C0127

Threshold: Triggering of error "OC8"

0 ... 120 %

0 %

C0128

Thermal motor time constant

0.1 ... 50.0 min

5.0 min

C0606

Response to error "OC8"

TRIP, warning, off

Warning

Calculate release time and I

2

x t load

Formula for release time

Information

t

+ * ( t ) ln

ȧȧ

ȡ
Ȣ

1

*

z

) 1

ǒ

IMot

IN

Ǔ

2

100

ȧȧ

ȣ
Ȥ

I

Mot

Actual motor current (C0054)

I

r

Rated motor current (C0088)

t

Thermal motor time constant
(C0128)

z

Threshold value in C0120 (OC6) or
C0127 (OC8)

Formulae for I

2

x t load

Information

L(t)

+

ǒ

I

Mot

I

N

Ǔ

2

100%

ǒ

1

* e

*t

t

Ǔ

L(t)

Chronological sequence of the
I

2

x t load of the motor

(Display: C0066)

I

Mot

Actual motor current (C0054)

Ir

Rated motor current (C0088)

t

Thermal motor time constant
(C0128)

If the controller is inhibited, the I

2

x t load is reduced:

L(t)

+ L

Start

e

* tt

Ǹ

L

Start

I

2

x t load before controller inhibit

If an error is triggered, the value
corresponds to the threshold
value set in C0120 (OC6) or C0127
(OC8).