3 technical data, General data and operating conditions, Technical data – Lenze ECSCx Axis cold plate User Manual

Page 89: 3technical data

Advertising
background image

Technical data

General data and operating conditions

3

l

89

EDKCSCX064 DE/EN/FR 4.0

3

Technical data

3.1

General data and operating conditions

Standards and operating conditions

Conformity

CE

Low−Voltage Directive (2006/95/EG)

Approvals

UL 508C

Power Conversion Equipment
Underwriter Laboratories (File No. E132659)
for USA and Canada

CSA 22.2 No. 14

Max. permissible
Motor cable
length

shielded

50 m

For rated mains voltage and switching frequency of
8 kHz

Packaging (EN ISO 4180)

Shipping package

Installation

l

Installation into IP20 control cabinet

l

For the "safe torque off" function (formerly "safe standstill"):
mounting in IP54 control cabinet

Mounting position

vertically suspended

Free space

above

³ 65 mm

below

³ 65 mm
With ECSZS000X0B shield mounting kit: > 195 mm

to the sides

can be mounted directly side by side without any clearance

Environmental conditions

Climate

3k3 in accordance with IEC/EN
60721−3−3
Condensation, splash water and ice
formation not permissible.

Storage

IEC/EN 60721−3−1

1K3 (−25 ... + 55 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (0 ... + 55 °C)

l

Atmospheric pressure: 86 ... 106 kPa

l

Above +40 °C: reduce the rated
output current by 2 %/°C.

Site altitude

0 ... 4000 m amsl

l

Reduce rated output current by
5 %/1000 m above 1000 m amsl.

l

Over 2000 m amsl: Use is only
permitted in environments with
overvoltage category II

Pollution

EN 61800−5−1, UL840: Degree of pollution 2

Vibration resistance

Acceleration resistant up to 0.7 g (Germanischer Lloyd, general conditions)

Advertising