Mechanical installation

Important notes

4

l

18

GHB 13.0001−EN EN 3.0

4

Mechanical installation

4.1

Important notes

ƒ

Use the controllers as built−in units only!

ƒ

In case of contaminated cooling air (dust, lints, greases, aggressive gases):
– Take suitable preventive measures, e.g. separate air duct, installation of filters,

regular cleaning, etc.

(

Stop!

Do not install drives on top of each other in the control cabinet!

ƒ

Observe installation clearances!
– You can install several controllers next to each other without free space in a

control cabinet.

– Ensure unimpeded ventilation of cooling air and outlet of exhaust air!
– Allow a free space of 100 mm at the top and at the bottom.
– If possible, the rear panel of the drive controller should be provided with a good

thermal connection to the control cabinet wall.

– In case of high load and a bad heat dissipation, the drive controller reduces the

drive power, or possibly switches off.

ƒ

Do not exceed the range of the ambient operation temperature specified in the
Technical Data.

ƒ

In case of permanent oscillation or agitation:
– Check whether shock absorbers are necessary.

Possible mounting positions:

Vertically on the control cabinet rear panel with mains terminals at the top.