7 communication, 1 connection of digital frequency coupling at x10, Communication – Lenze E931Ex User Manual

Page 29: Connection of digital frequency coupling at x10, Electrical installation, 120 w, Connection plan

Advertising
background image

Electrical installation

Communication

Connection of digital frequency coupling at X10

5

l

29

GHB 13.0001−EN EN 3.0

5.7

Communication

ƒ

In order to provide for a perfect operation, we recommend the use of Lenze system
cables. (

42)

ƒ

Check the plug connections of the bus cables with regard to a tight fit.

5.7.1

Connection of digital frequency coupling at X10

ƒ

Master frequency features:

– Angular resolution / number of increments max. 12 bits / 1024 increments

switchable to 512 / 256 / 128 / 64 and 32 increments

– Track signals A, B, Z in accordance with RS422 standard

– Output impedance R

a,diff

= 120

W

Technical data master frequency

Output X10

Input X10

l

Output frequency: 0 ... 500 kHz

l

Current capacity per channel: max 20mA.

l

Two−track with inverse 5 V signals (RS422) and zero
track

l

In case of a parallel connection maximally three
slave drives can be connected

l

By LOW level, PIN 8 (enable) indicates the
initialisation of the master drive (e. g. when the
mains has been switched off in the meantime). This
enables the slave drive to monitor the master.

l

Input frequency:
– 0 ... 500 kHz for TTL level

l

Max. 5 mA

l

Two−track with inverse signals and zero track
– With regard to incremental encoders with HTL

level, also operable without reversed signals

Connection plan

B

B

GND

GND

GND

GND

Z

Z

1

2
3
4
5
6
7
8
9

1

2
3
4
5
6
7
8
9

A

A

X10

X10

< 15 m

A

A

B

B

Z

Z

A

A

B

Z

B

Z



931E−003.cdr

Fig. 6

Connection of digital frequency input and digital frequency output (X10)

X10 Slave drive



Signals with CW rotation

X10 Master drive

Cores twisted in pairs

Assignment of 9−pin Sub−D socket (X10) at the controller for digital frequency coupling

Pin

1

2

3

4

5

6

7

8

9

Signal

A

B

Z

GND

n. c.

A

B

Z

GND

0.14 mm

2

(AWG 26)

0.5 mm

2

(AWG 20)

0.14 mm

2

(AWG 26)

0.5 mm

2

(AWG 20)

0.14 mm

2

(AWG 26)

Advertising