Initial switch−on

6

l

36

GHB 13.0001−EN EN 3.0

10. Parameterise the digital terminals in the "Parameters

W I/Os... W Digital inputs"

menu.
– Terminal assignment see connection example. (

22)

– The analog inputs may not be configured as digital inputs. Therefore, in the

"Parameters

W IOs W Digital inputs" menu, check whether the selection

"Interprete AINs as DINs" is not set! Otherwise you are not able to evaluate the
analog setpoint.

– The function of the digital inputs can be displayed under the menu item "Function

overview". Check the right function here.

– The 931E Software Manual decribes how you configure analog inputs as digital

inputs.

931E_011

11. Set the threshold for the undervoltage recognition in the "Parameters

W Drive

parameters

W DC bus monitoring…" menu.

– Adjust the threshold according to the application and the supply voltage (e. g. 16 V

for 24 V DC power supply).

The basic settings are now completed.