Troubleshooting and fault elimination

Error message

7

l

39

GHB 13.0001−EN EN 3.0

7.2

Error message

Various monitoring functions protect the drive against impermissible operating
conditions. If a monitoring function is activated, a response corresponding to the
protection of the drive is actuated. The following things are monitored:

ƒ

Temperature of the output stage

ƒ

Motor temperature

ƒ

I2t monitoring of the motor

ƒ

Overcurrent / short circuit of the output stage

ƒ

DC−bus voltage (under− and overvoltage)

ƒ

Following error with regard to position control

ƒ

Error with regard to the reference run

ƒ

Error with regard to the angle encoder system

ƒ

Communication error

ƒ

Initialisation error

ƒ

Check sum error of the parameters

Some responses to failures can be set within the SDC parameterisation software. Possible
responses are:

Reaction

Meaning

Reaction of the drive

A

Immediate disconnection of the
output stage

The motor coasts.

h

Emergency stop

The motor is braked to zero speed at the current limit. If there
is a motor holding brake, it is applied. The output stage
switches off.

W

Warning

The controller keeps operating, the output stage remains
switched on. The warning signal can be read out via the CAN
bus or via the serial RS232 interface.

O

Off

The warning signal is inhibited − no response.

Used symbols:

Symbol

Meaning

þ

Default setting

¨

Response parameterisable in SDC

Selection not possible