Electrical installation, Stop – Lenze E931Ex User Manual

Page 24

Advertising
background image

Electrical installation

Voltage supply

5

l

24

GHB 13.0001−EN EN 3.0

(

Stop!

The maximum permissible current loading of the terminal strip X2 is 16 A per
terminal. If required, the supply voltage has to be connected in parallel!

X2 supply voltage

Pin No. Designation

Value

Specification

1

UL

24 ... 48 V

DC−bus voltage output stage

2

As 1, loop through of the supply to further drives

3

BR

Connection external brake resistor against UL

4

24 V

+24 V / 1.5 A

Control voltage for control section, DOUT0, DOUT1, DOUT2 and holding
brake, max. 1.5 A

5

As 4, loop through of the supply to further drives

6

GND

0 V

Common reference potential for the DC−bus voltage and control voltage

7

As 6, loop through of the GND potential to further drives

Terminal data

Max. conductor cross−section

Tightening torque

Screw drive

Cable

[mm

2

]

[AWG]

[Nm]

[lb−in]

Flexible

7 mm

2.5

12

0.5 ... 0.6

4.4 ... 5.3

Slot 0.6 x 3.5

With wire end
ferrule

External brake resistors

(

Stop!

The drive controller does not monitor the temperature of the external resistor.
For this purpose, additional safety measures are to be considered!

The drive controller is provided with an integrated brake resistor which is designed for a
permanent power of 10 W or for a pulse power of 200 W for 50 ms.

If higher permanent or pulse powers are required, you can connect an additional external
brake resistor to the integrated brake chopper.

If the switching threshold of the brake chopper is exceeded, both resistors are energised.

Parameter

Value

Switching threshold brake chopper on

Approx. 63 V

Switching threshold brake chopper off

Approx. 60 V

Resistance, external

> 5

W

Rated power

10 W ... 600 W