Electrical installation

Motor connection

5

l

25

GHB 13.0001−EN EN 3.0

5.4

Motor connection

ƒ

For trouble−free operation, we recommend to use Lenze standard cables.

ƒ

Ensure a proper shielding of the motor and feedback cable to avoid interferences.

X3 motor connection

Pin No.

Designation

Specification

1

U

Motor phases
Fundamental wave in case of
overload for 2 s up to 32 A

eff

approx. 0 V ... 27 V

eff

2

V

0 V ... 13 A

eff

3

W

0 Hz ... 200 Hz

4

BR+

Brake

24V DC

5

BR−

0 V

Terminal data

Max. conductor cross−section

Tightening torque

Screw drive

Cable

[mm

2

]

[AWG]

[Nm]

[lb−in]

Flexible

7 mm

2.5

12

0.5 ... 0.6

4.4 ... 5.3

Slot 0.6 x 3.5

With wire end
ferrule

(

Stop!

The brake is supplied by the control voltage at X2. In order to ensure the
trouble−free operation of the brake, the control voltage has to be in the
tolerance range of the brake used!