Electrical installation

Communication
Connection of CAN bus at X4.1 and X4.2

5

l

30

GHB 13.0001−EN EN 3.0

5.7.2

Connection of CAN bus at X4.1 and X4.2

Features

ƒ

Parameter presettings

ƒ

Data exchange from controller to controller

ƒ

Connection of operator and input devices

ƒ

Connection of external controls and control systems

ƒ

Baud rate 125, 250, 500 kBaud

(

Stop!

For the termination of the bus system, an external 120

W terminating resistor is

required.

Connection plan

X4.1 / X4.2

931E−001.iso

Fig. 7

Connection of CAN bus (X4.1, X4.2)

Pin no.

Meaning

Comment

1

CAN−HIGH

CAN−HIGH (high is dominant)

2

CAN−LOW

CAN−LOW (low is dominant)

3

CAN−GND

CAN ground

4

Ċ

Reserved

5

Ċ

Reserved

6

CAN−SHLD

CAN shield (hardware version 1.1 and higher)

7

CAN−GND

CAN ground

8

Ċ

Reserved

I

Tip!

An RJ45 bus terminating connector is available for the 931E drive controllers.
Please contact Lenze.