5 output module, Output module, Technical data – Lenze ETCxxxxx User Manual

Page 12

Advertising
background image

Technical data

Rated data
Output module

2

2.2
2.2.5

l

12

EDSTCXX EN 2.0

2.2.5

Output module

Type

ETCHU008

ETCHU016

Use

Semiconductor switch against 24 V DC (High Side Switches)

8 channel output module

16 channel output module

Weight

145 g

215 g

Dimensions (H x W x D)

99 x 22.5 x 114.5 mm

99 x 45.0 x 114.5 mm

Supply voltages:

Supply voltage outputs

typ. 24 V DC (18 ... 32 V DC) external feed

Supply voltage control

typ. 24 V DC (18 ... 32 V DC) via ME bus

Logical voltage

typ. 5.0 V DC (4.75 ... 5.24 V DC) via ME bus

Power loss:

4 outputs switched on

typ. 1.0 W

8 outputs switched on

typ. 1.8 W

typ. 1.5 W

16 outputs switched on

typ. 3.0 W

Outputs:

Switching voltage

typ. 24 V DC (18 ... 32 V DC) external feed

Load characteristic

resistive, inductive, capacitive

Continuous current per
channel

max. 500 mA

Current per channel for 1 sec

700 mA

Voltage drop for switch

max. 400 mV at 500 mA

Min. voltage at the output
terminals

Supply voltage – 1.0 V (at full load 0.5 A)

Parallel switching of several
outputs

possible

Switching frequency of the
switches

max. 250 Hz at resistive load

Restart

automatically after short circuit (with control present)

Short circuit peak current

transient 4.0 A per channel (limited in the switch)

automatic restart current
with sustained short circuit
at output

3.0 A pulsed (with control present) switched off

Output indication

on LED per output at the switch output

Initial state witch missing
control switched off by

logical component

Intermediate storage of the
control signal

no

Electrical isolation

The output earth conductors are connected to each other

Fuse:

Switch

Per 4 outputs each time−lag Microfuse 4 A; optionally pluggable

Switch triggering

SMD time−lag fuse 500 mA

Logic component

SMD time−lag fuse 500 mA

Power recovery

up to max. + 32 V DC at one output terminal possible

Potential isolation

500 V DC (between logic component and input terminal)

Protection

l

The outputs are protected against overheating, short circuit and polarity reversal up to

±

32 V DC.

l

Additional fire protection with 4 A fuse. Suppressor diode (36 V) parallel to each switch
output.

l

Series diode between switch output and output terminal.

l

RESET trigger with drop in logical voltage.

Advertising