6 analogue module, Analogue module, Technical data – Lenze ETCxxxxx User Manual

Page 13

Advertising
background image

Technical data

Rated data

Analogue module

2

2.2

2.2.6

l

13

EDSTCXX EN 2.0

2.2.6

Analogue module

Type

ETCHA022

Use

2 channel analogue input/output module, 0 V or −10 V ... +10 V

Weight

125 g

Dimensions (H x W x D)

99 x 22.5 x 114.5 mm

Supply voltages:

Control voltage (sensor feed)

typ. 24 V DC (18 ... 32 V DC) feed via ME bus

Logical voltage

typ. 24 V DC (18 ... 32 V DC) feed via ME bus

Power loss

max. 6.2 W

Input:

Input impedance

> 500 kOhm

Measuring range
(switchable)

0 ... 10 V or –10 V ... +10 V

Voltage at the input

max. 32 V

Resolution

12 Bit

Conversion method

successive approximation

Value of the LSB

2.5 mV for measuring range 0 ... 10 V or

5 mV for measuring range −10 V ... +10 V

Inaccuracy

max. 50 mV for measuring range 0 ... 10 V or max. 100 mV for measuring range −10 V ... +10 V

Scanning frequency

205 Hz

Filters

analogue low−pass filter of 1st degree with a limiting frequency of 30 Hz, digital configurable

low−pass filter

Permitted sensor types

Active and passive sensors

Sensor feed, sensor current

10 V regulated, max. 10 mA

Permitted connection cables

Shielded cables; shield placed before the module

Output:

Output range (switchable)

0 ... 10 V or −10 ... +10 V

max. 0 ... 10.238 V or −10.238 V ... +10.238 V

Output current

max. 2 mA

Min. load

5 kOhm

Resolution

12 Bit

Value of the LSB

2.5 mV or 5 mV

Inaccuracy

max. 50 mV or 100 mV

Output rate

min. 10 ms continually, min. 5 ms continually (digital input filter switched off)

Filters

analogue low−pass filter of 1st degree with a limiting frequency of approx. 730 Hz

Permitted connection cables

Shielded cables, shield placed before the module

Power recovery

max.

±

32 V at an input/output terminal

Potential isolation

500 V DC between ME bus and input/output terminals

Fuse:

Logic component

SMD time−lag fuse 500 mA

System voltage

SMD time−lag fuse 1500 mA

Protection

l

24 V system voltage is protected by a definite plug−in direction in the housing.

l

5 V bus voltage is protected by a definite plug−in direction in the housing.

l

Sensor supply is protected against short circuit, overcurrent and negative feed

l

Current and voltage inputs (optional) are protected against voltages up to 32 V

l

Input protection via high resistance voltage dividers

l

Protection of the sensor feed via series diodes and active current limitation

l

ESD protection via Transil diodes at PE

l

Output protection via passive current limitation

l

Series and parallel diodes, short−circuit proof

l

ESD protection via Transil diodes at PE