Troubleshooting and fault elimination

Error management

6

6.2

l

62

EDSTCXX EN 2.0

6.2

Error management

Problem

Potential cause

Remedy

LED 24 V at the power supply
unit does not illuminate

24 V power supply at the
power supply unit missing

Check 24 V supply
Check fuse

Internal short circuit in the
module

Check or replace module

LED 5 V at the power supply
unit does not illuminate

Internal short circuit in the
module

Check or replace module
Check fuse

CAN bus does not work
properly

Switch position S1 wrong

Check switch position S1

Problem

Potential cause

Remedy

CAN bus is not continued in
the module

Internal short circuit in the
module

Check or replace module

CAN bus does not work
properly

Switch position S1 wrong

Check switch position S1

Problem

Potential cause

Remedy

Module does not work

ME bus contacts incorrect

Check module

24 V power supply at the
power supply unit missing

Check 24 V supply

Internal module fault

Replace module

Live LED does not illuminate

Internal 24 V short circuit, PTC
has triggered

Remove short circuit, wait a
few seconds

Live LED is programmed
differently

Check parameterisation

Live LED illuminates, no input
LED, in spite of signal

Signal not present

Check signal at module

24 V signal present, input LED
illuminates, but signal is
processed as 0

Input parameterised with
inverse logic

Check parameterisation

Brief input signal is not
detected

Debouncing active

Check parameterisation

Problem

Potential cause

Remedy

Module does not work

ME bus contacts incorrect

Check module

24 V power supply at the
power supply unit missing

Check 24 V supply

Internal module fault

Replace module

Live LED does not illuminate

Internal 24 V short circuit, fuse
has triggered

Replace module

Live LED is programmed
differently

Check parameterisation

Live LED illuminates, no
output LED in spite of signal

Signal not present

Check signal at module

24V voltage present, output is
0, output LED does not
illuminate, but signal is
present

Input parameterised via CAN
bus as inverse logic

Check parameterisation

ETCHN003

ETCHT000

ETCHI008/ETCHI016

ETCHU008/ETCHU016