Device description – Lenze ETCxxxxx User Manual

Page 17

Advertising
background image

Device description

System overview

Layout example for an ETC island

3

3.1

3.1.2

l

17

EDSTCXX EN 2.0

CAN bus terminated

1. isolated system

max. CAN bus length

Control

CAN Master

2. isolated system

3. isolated system

ETC024

Several ETCHx islands can be connected to form a complete system. Please
note the maximum permissible cable length per CAN level dependent on the
Baud rate (

56). The maximum number of modules in one ETCHx island is

limited by the following constraints.

CAN Bus

max. 127 modules

Module address

max. 16 modules of the same type

Power supply
unit

In practice the capacity of the power supply unit is the decisive factor for
the maximum number of modules in an island. The current consumption of
the individual modules both via the 24 V and the 5 V supply is relevant and
must be taken into account.
Typically 15 modules can be supplied with one power supply unit
ETCHN003.

The power consumption of the individual modules fromthe 5 V voltage
produced in the power supply unit is shown in the following table.

The figure for "typ." refers to the 24 V supply voltage and with a high signal
being present at half the digital inputs and outputs.

The figure for "max." refers to the 32 V supply voltage and an operating state
with maximum power consumption.

Module

5 V internal bus

24 V internal bus

24 V external (no load)

typ.

max.

typ.

max.

typ.

max.

ETCHU00895 mA

180 mA

15 mA

30 mA

30 mA

80 mA

ETCHU016

130 mA

240 mA

25 mA

55 mA

60 mA

160 mA

ETCHI008

70 mA

90 mA

90 mA

105 mA

ETCHI016

90 mA

120 mA

145 mA

175 mA

ETCHA022

150 mA

160 mA

60 mA

80 mA

ETCHU008/016: Outputs fed externally.
ETCHI008/016: Eingänge intern gespeist.

The ampacity of the cables and plug−in connectors of the internal system bus
is at least 8 A (per cable). The direct plug−in connections between housing
and PCB can accept a load of 3 A.