3 set node address, Set node address, Device description – Lenze ETCxxxxx User Manual

Page 18

Advertising
background image

Device description

System overview
Set node address

3

3.1
3.1.3

l

18

EDSTCXX EN 2.0

3.1.3

Set node address

Every ETCHx I/O module in a line represents a separate node at CAN1 bus and
must be set up with a unique node address.

ETC025

The node address is set via a front Hex switch (4 low value address bits) and
via permanently wirded bridges within the housing (3 high value address
bits). This means that a maximum of 16 modules are possible within a
module type.

)

Note!

Some modules have internal codings switches instead of the
permanently wired bridges for the optional modification of the
high value address bits.

Module type

High value

address bits

permanently

wired

Low value

address bits

adjustable at

the front

Adjustable

node address

(hex)

Adjustable

node address

(decimal)

CAN Bus Master

−−

−−

00

0

−−

−−

−−

01 H

0 FH

1 ... 15

ETCHU

10 H

0

FH

10 H

1 FH

16 ... 31

20 H

0

FH

20 H

2 FH

32 ... 47

ETCHA

30 H

0

FH

30 H

3 FH

48 ... 63

40 H

0

FH

40 H...4 FH

64 ... 79

ETCHI

50 H

0

FH

50 H

5 FH

80 ... 95

60 H

0

FH

60 H ... 6 FH

96 ... 111

70 H

0

FH

70 H ... 7 FH

112 ... 127

)

Note!

All modules at the CAN bus must have a different node address.