Device description
Module
Power supply unit
3.4
3.4.1
l
33
EDSTCXX EN 2.0
9 ... 12
LED 5 V, LED 24 V
F1
S1, S2
ME
1 ... 4
ETC007
Terminal
Designation
Meaning
Comment
1
+24 V
Voltage supply
2
0 V
Reference potential
9
C_H
CAN High
To extend the ME bus
to external modules
10
C_L
CAN Low
11
C_Gd
CAN signal earth
12, 3, 4
CAN shield potential, shielding
Terminals bridged
internally
S1
Switch for CAN bus termination
On = termination with
120 Ohm between C_H
and C_L
F1
Fuse
Plug−in Microfuse 5 A,
125 V (manufacturer
Wickmann No.
303−1500−042); pull to
replace
LED 5 V
Live LED 5 V and 24 V
Illuminate if voltage is
adequate
LED 24 V
ME
ME bus
Elements