3 stub cables, Stub cables, Electrical installation – Lenze ETCxxxxx User Manual

Page 57

Advertising
background image

Electrical installation

CAN installation instructions

Stub cables

5

5.2

5.2.3

l

57

EDSTCXX EN 2.0

5.2.3

Stub cables

Stub cables are permitted. Their maximum length at 125 kB/s must not
exceed 1 m (or 30 cm for 1 Mbit/s) per stub cable.

With several stub cables the total of the stub cable lengths must not exceed
30 m (for 500 kbit/s).

The sub cable connections are made in the terminal box parallel to the CAN
bus. Sub cables are not terminated with a resistor.

CAN bus not

terminated

branch line max. 1 m

CAN bus

terminated

clamping box

1. isolated system

Control

CAN Master

2. isolated system

4. isolated syst.

3. isolated system

ETC041