2 rated data, 1 standard device, Rated data – Lenze ETCxxxxx User Manual
Page 9: Standard device, Technical data
Technical data
Rated data
Standard device
2.2
2.2.1
l
9
EDSTCXX EN 2.0
2.2
Rated data
2.2.1
Standard device
Type
ETCHx
ETCPx
Use
Control (top hat rail design)
Control (PCI insert card)
Weight
235 g
300 g
Dimensions (W x H x D)
100 x 45 x 115 mm
130 x 23 x 190 mm
Supply voltages:
Feed (external)
typ. 24 V DC
5 V DC output on ME bus
typ. 5.0 V, min. 4.75 V, max. 5.25 V DC
24 V DC output on ME bus
typ. 24 V, min. 18 V, max. 32 V DC
Power loss
max. 3 W
Power recovery
up to max.
±
32 V possible at the connection terminals
Potential isolation:
to CAN
via optocoupler
to process level
via optocoupler
Fuse:
24 V DC output on ME bus
Front panel fuse
5 V DC output
Short−circuit proof via DC/DC converter
Protection:
Feed
against polarity reversal
5 V and 24 V supply
against short circuit and polarity reversal