Troubleshooting and fault elimination – Lenze ETCxxxxx User Manual

Page 63

Advertising
background image

Troubleshooting and fault elimination

Error management

6

6.2

l

63

EDSTCXX EN 2.0

Problem

Potential cause

Remedy

Module does not work

ME bus contacts incorrect

Check module

24 V power supply at the
power supply unit missing

Check 24 V supply

Internal module fault

Replace module

Live LED does not illuminate

Live LED is programmed
differently

Check parameterisation

Current is not detected
correctly

Wrong parameterisation

Check parameterisation and
calibration

Wrong sensor supply

Measure the supply voltage of
the sensor

PTC fuse has triggered

Check sensor for short circuit

ETCHA022