4 technical data, Technical data, Technical data 4 – Lenze EMZ9374IB User Manual

Page 50: 4technical data

Advertising
background image

Technical data

4

l

50

EDBMZ9374X DE/EN/FR 4.2

4

Technical data

General data

Field

Values

Electrical connection

Power supply

+18 ... +30 VDC

Current consumption

80 mA at +24 VDC

Digital outputs

Features

l

No electrical isolation

l

Protected against short−circuits

Current per output

max. 1 A

HIGH level

+13 ... +30 VDC

LOW level

0 ... +5 VDC

Digital inputs

Features

No electrical isolation

Input resistance

3 k

W ... 4 k W

HIGH level

+13 ... +30 VDC

LOW level

0 ... +5 VDC

System bus (CAN)

Protocol

with reference to CANopen
(matched with the Lenze automation
components)

Communication medium

DIN ISO 11898

Network topology

Line
(terminated at both ends with 120

W)

System bus device

Slave

max. number of devices

63

Baud rate [kBit/s]

20

50

125

250

500

1000

max. bus length [m]

2500 1000 500

250

80

25

Weight

110 g

Operating conditions

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1 1K3 (−25 ... +70 °C)

Transport

IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3 3K3 (0 ... +55 °C)

Permissible moisture

Humidity class F without condensation (medium relative humidity
85 %)

Enclosure

IP20

Maintenance

Free of maintenance