Application examples

93XX controller with two terminal extensions

9

l

78

EDBMZ9374X DE/EN/FR 4.2

Terminal extension settings in the programming mode

Terminal extension 1 (9374 master)

Terminal extension 2 (9374 slave1)

DIP switch

Status

Function

DIP switch

Status

Function

1

OFF

Terminal I/O1 = Input

1

ON

Terminal I/O1 = Output

2

OFF

Terminal I/O2 = Input

2

ON

Terminal I/O2 = Output

3

OFF

Terminal I/O3 = Input

3

ON

Terminal I/O3 = Output

4

OFF

Terminal I/O4 = Input

4

ON

Terminal I/O4 = Output

5

OFF

Terminal I/O5 = Input

5

ON

Terminal I/O5 = Output

6

OFF

Terminal I/O6 = Input

6

ON

Terminal I/O6 = Output

7

OFF

Terminal I/O7 = Input

7

ON

Terminal I/O7 = Output

8

OFF

Terminal I/O8 = Input

8

ON

Terminal I/O8 = Output

Setting sequence:
1. Switch on the power supply for the terminal extension.
2. Set the DIP switch 12 to ON (programming mode).

LED "ERROR module" is flashing and LED "operation" is off.

3. Configure the terminals I/O1 ... I/O8 using the DIP switches 1 ... 8.

For the DIP switch states see table above.

4. Set the DIP switch 12 to OFF (operating mode).

The configuration of the inputs/outputs is completed.

5. Switch off the power supply for the terminal extension.

The programming mode is quit only after the power supply has been
switched off.