Application examples

93XX controller with two terminal extensions

9

l

77

EDBMZ9374X DE/EN/FR 4.2

Controller settings

(Please also note the specifications in the system manual of the controller).
Setting sequence:
1. Set CAN bus node address to value 1 (C0350 = 1).
2. Address for CAN3−IN and CAN3−OUT is to be determined by C0350

(C0353/3 = 0).

3. Set CAN bus baud rate to 500 kBit/s (C0351 = 0).
4. Set CAN bus master operation (C0352 = 1).
5. Set cycle time for cyclic process data transfer (C0356/3 > 0).
6. Change process output words in CAN3−OUT to digital output signals

(C0864/3 = 1).

7. Save set parameters (C0003 = 1).
8. Activate CAN reset node (C0358 = 1).

(

Stop!

When status information is sent from the terminal extension, the
entire byte is read into the controller, including the status
information of the digital outputs.

ƒ

In the example, the input states are read via
CAN3−IN.B0 ... CAN3−IN.B7 and the output states via
CAN3−IN.B8 ... CAN3−IN.B15.

ƒ

Check the internal links of the input signals
CAN3−IN.B8 ... CAN3−IN.B15 at the controller. Set outputs (HIGH
level) of the terminal extension may trigger uncontrolled actions
on the controller.