Electrical installation

Wiring of the system bus (CAN)

6

l

56

EDBMZ9374X DE/EN/FR 4.2

6.4

Wiring of the system bus (CAN)

Principle structure

120 W

120 W

A

1

9374-Master

GND

LO

HI

PE

GND

LO

HI

PE

A

n

GND

LO

HI

PE

A

2

9374-Slave1

GND

LO

HI

PE

9374-Slave2

GND

LO

HI

PE

9374-Slave3

GND

LO

HI

PE

9374_005

A

1

Bus device 1 (controller)

A

2

Bus device 2 (9374 master)

A

n

Bus device n (n = max. 63)

9374 slave1 ... 9374 slave3 communicate with 9374 master (only bus device A

2

)

ƒ

Only terminals of the same type must be connected

ƒ

Connection of the bus terminating resistors:

One resistor 120

W on the first and last bus device .

Features:

ƒ

CAN−based with bus protocol according to CANopen (CAL−based
Communication Profile DS301)

ƒ

Bus expansion:

25 m for max. 1 Mbit/s baud rate

up to 1 km with reduced baud rate

ƒ

Extremely reliable data transmission (Hamming distance = 6)

ƒ

Signal level to ISO 11898

ƒ

Up to 63 bus devices are possible

Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W

(95 ... 140

W

)

Cable resistance

Cable length

£ 300 m £ 70 m

W

/m

Cable length

£ 1000 m £ 40 m

W

/m

Signal propagation delay

£ 5 ns/m