Commissioning

Configuration with internal DIP switches

Settings in the operating mode (normal operation)

7

l

63

EDBMZ9374X DE/EN/FR 4.2

Setting the CAN bus baud rate

DIP switch

Baud rate [kBit/s]

1000

500

250

125

100

50

20

10

9

OFF

OFF

OFF

OFF

ON

ON

ON

ON

10

OFF

OFF

ON

ON

OFF

OFF

ON

ON

11

OFF

ON

OFF

ON

OFF

ON

OFF

ON

ƒ

Set the baud rate of the terminal extensions with the DIP switches 9 ... 11.

The baud rate of the terminal extension must be identical with the baud
rate of the controller (master).

In the Lenze default setting, the master has the baud rate 500 kBit/s
(C0351 = 0).

)

Note!

The baud rate to be set depends on the length of the system bus
cable. (

50, Technical data)