1 settings in the programming mode, Settings in the programming mode, Commissioning – Lenze EMZ9374IB User Manual

Page 59

Advertising
background image

Commissioning

Configuration with internal DIP switches

Settings in the programming mode

7

l

59

EDBMZ9374X DE/EN/FR 4.2

7.3.1

Settings in the programming mode

Digital inputs and outputs (terminals I/O1 ... I/O8) are configured in the
programming mode .

DIP switch assignment in the programming mode

DIP switches

Function

Setting notes

Note

1

Terminal I/O1 Set the DIP switches according to the

terminal assignment I/O1 ... I/O8:

l

DIP switches ON: Terminal
configured as output

l

DIP switches OFF: Terminal
configured as input

An error message is
displayed (LED

ERROR" on), if a

terminal is configured
as output and a HIGH
level is applied.

2

Terminal I/O2

3

Terminal I/O3

4

Terminal I/O4

5

Terminal I/O5

6

Terminal I/O6

7

Terminal I/O7

8

Terminal I/O8

9

Set DIP switch to OFF

10

Set DIP switch to OFF

11

Set DIP switch to OFF

12

Programming

mode /

Operating

mode

Set DIP switch to ON
(Programming mode)

In the programming
mode

l

LED

ERROR module" is

flashing

l

LED

Operation" is off

Setting sequence:
1. Switch on the power supply for the terminal extension.
2. Set DIP switch 12 to ON (programming mode).
3. Configure the terminals I/O1 ... I/O8 using DIP switches 1 ... 8.
4. Set DIP switch 12 to OFF (operating mode).

The configuration of the inputs/outputs is completed.

5. Switch off the power supply for the terminal extension.

The programming mode is quit only after the power supply has benn
switched off.