Settings in the operating mode (normal operation), Commissioning – Lenze EMZ9374IB User Manual

Page 60

Advertising
background image

Commissioning

Configuration with internal DIP switches
Settings in the operating mode (normal operation)

7

l

60

EDBMZ9374X DE/EN/FR 4.2

7.3.2

Settings in the operating mode (normal operation)

(Carry out settings only when the power supply is switched off!)
In the operating mode carry out the following settings:

ƒ

Addressing of the terminal extension

ƒ

Number of terminal extensions used

ƒ

Setting the CAN bus baud rate

DIP switch assignment in operating mode

DIP switch

Function

Setting notes

Note

1

Setting the
CAN bus
node address

DIP switches 1 ... 6 are used to set the
address of the terminal extension.
The table "Addressing of the terminal
extension" shows the switch settings.

A maximum number
of 63 addresses are
available.

2

3

4

5

6

7

Number of
terminal
extensions
on one
address

You can operate maximal 4 terminal
extensions on one device address.

8

9

Baud rate
setting

The table "Setting the baud rate" shows
the switch settings.

^

63

10

11

12

Programming

mode /

Operating

mode

Set the DIP switch to OFF (operating mode)

When the operating
mode is set, the LED
"operation" is on.

Set operating mode:
1. Check whether DIP switch 12 is set to OFF (operating mode).
2. Switch on the power supply for the terminal extension.

Operating mode is active.